Quick answer — A Buchholz relay senses gas accumulation and oil surge in the pipe between the transformer and the conservator. A slow gas accumulation (from a minor fault) gives an alarm; a large gas or oil surge (from a major fault) trips the transformer. The gas can be collected and analysed to diagnose the fault. It is fitted on oil-filled units above a certain size.
Contents
How does a Buchholz relay operate?

What it senses

It has a gas (and sometimes a surprise) element and an oil-surge element. Gas collects under the relay from a minor fault and gives a low alarm; a violent fault causes gas and an oil surge that trips the unit.

Alarm vs trip

Slow gas accumulation trips the alarm and flags a developing fault; a major gas or surge trips the breaker to disconnect the transformer, protecting it.

Diagnosis

The collected gas is analysed (combustible, CO2, etc.) and the DGA used to identify whether it is a thermal, partial-discharge or arcing fault.

References & standards

Related

Book seriesAcademy

Related manufacturers

Prolec GE (GE Vernova) · Prolec GE Waukesha · Hitachi Energy USA · Siemens Energy · Eaton · Virginia Transformer Corp

Related components

Protection, monitoring & diagnostics Oil, fluids & preservation
Technical content is prepared from engineering references, standards frameworks, manufacturer documentation and industry sources. Contractual or compliance decisions should refer to current official standards. TransformerPath Technical Editorial.
Source transformers for this application

Submit an RFQ or browse manufacturers and components.

Submit an RFQ Get Verified