What Is Insulation Coordination?
The idea
You choose the insulation strength (BIL) of equipment so it survives the normal and switching voltage, and the clearances, so that any surge is diverted by arrester protection before it threatens the asset. The cost rises with BIL, so the design balances cost and risk.
How it works
Arresters limit the surge voltage to a value below the equipment BIL, with a margin; the BIL increases with system voltage. Coordination ensures the BIL of the transformer (or bushing) is above the protective level of the arrester. A transformer at a given system voltage has a defined BIL and test levels. It is given as e.g. 110 kV system, 550 kV BIL.
Applied and induced tests
The applied (power-frequency) test proves the insulation to earth and between windings; the induced test proves the inter-turn insulation. Both are specified with the insulation level.
Why it matters
It prevents insulation failure from lightning or switching surges and ensures that, if a failure does occur, it is at a location and component that is cheaper and safer to replace.
References & standards
- IEC 60071 (insulation coordination)
- IEC 60076-3
- IEEE C57.12.00