What Is a Transformer Temperature Rise Test?

Published 27 Aug 2026Updated 27 Aug 20266 min readIntermediateTesting
Quick answer — A temperature rise (heat run) test confirms the transformer can carry its rated load without exceeding the specified oil and winding temperature rise. The transformer is loaded (or run at the equivalent loss) until the temperatures stabilise, then the oil and winding, and hottest-spot temperatures are measured and compared against the limits (e.g. 65 K rise for some IEEE designs, IEC using the appropriate class). It verifies the cooling design.
Contents
What is a temperature rise test on a transformer?

What it proves

It verifies that the cooling system can hold the oil and winding temperature rise within the design limit at the rated (or specified) load.

How it is run

The transformer is loaded to give the rated loss (often by running at rated current, or by a short-circuit back-to-back heat run), and the temperatures are read once they stabilise. The winding temperature is derived from resistance change and the hottest-spot from the design gradient.

Why it matters

It validates the cooling, confirms the insulation is within its thermal class, and is a type test that establishes the allowed loading.

References & standards

Related

Book seriesAcademy

Related manufacturers

Prolec GE (GE Vernova) · Prolec GE Waukesha · Hitachi Energy USA · Siemens Energy · Eaton · Virginia Transformer Corp

Related components

Transformer cooling systems Protection, monitoring & diagnostics
Technical content is prepared from engineering references, standards frameworks, manufacturer documentation and industry sources. Contractual or compliance decisions should refer to current official standards. TransformerPath Technical Editorial.
Source transformers for this application

Submit an RFQ or browse manufacturers and components.

Submit an RFQ Get Verified