How Does the Cooling Class Affect the Transformer Rating?
Quick answer — The cooling class (ONAN, ONAF, OFAF, OFWF/ODAF) directly sets the rated output. Natural cooling (ONAN) is the lowest rating, and adding fans (ONAF) or pumps (OFAF) raises the rating of the same unit for a given temperature rise. The nameplate gives the rating per cooling stage, e.g. 40 MVA ONAN and 60 MVA ONAF. A better cooling class gives a higher rating, but uses auxiliaries that need a supply.
How does the cooling class affect a transformer rating?
ONAN, ONAF, OFAF
ONAN is fully natural and lowest-rated; ONAF adds fans; OFAF/ODAF adds both fans and pumps, giving a higher rating for the same unit.
Multi-stage rating
A unit is often nameplated at different ratings per cooling stage (e.g. ONAN and ONAF), and the load is set by which stage is running.
The trade-off
A higher cooling class gives a smaller, lighter unit but requires auxiliary power and a loss of auxiliaries handling; the design and the loading guide set the safe use.
References & standards
- IEC 60076-2
- IEC 60076-7
Related
Related manufacturers
Prolec GE (GE Vernova) · Prolec GE Waukesha · Hitachi Energy USA · Siemens Energy · Eaton · Virginia Transformer Corp
Related components
Technical content is prepared from engineering references, standards frameworks, manufacturer documentation and industry sources. Contractual or compliance decisions should refer to current official standards. TransformerPath Technical Editorial.