What Is the OLTC Oil and How Is It Maintained?

Published 27 Aug 2026Updated 27 Aug 20265 min readIntermediateComponents
Quick answer — The OLTC has its own (often separate) oil in the diverter compartment. It is tested for the same condition (BDV, moisture, DGA) but the focus is on acetylene, which indicates contact arcing from a diverter/contact fault. The oil is changed on a schedule and when the acetylene rises. The tap-changer oil is a key maintenance point because an OLTC fault is a leading cause of transformer trips.
Contents
What is the on-load tap-changer oil?

Why separate oil

The diverter switches are in their own oil compartment so the arcing products are kept from the main oil, and the OLTC oil is tested and changed separately.

What to test

BDV, moisture and DGA, with the acetylene level indicating contact arcing. A rise in acetylene means the contacts/diverter need attention.

Maintenance

Change the oil and filter it per the schedule, check the contacts, and trip on the DGA rise to avoid a fault.