Auto ยท 400/220 kV interconnecting ยท YNa0(d) ยท series + common winding share one magnetic circuit ยท buried delta tertiary

Current path

Windings

View

Selected part

Click any part to identify it. An autotransformer shares one winding between HV and IV โ€” that is why it is smaller and cheaper than a two-winding unit at close ratios, but offers no galvanic isolation.
๐Ÿ–ฑ drag = orbit ยท wheel = zoom ยท right-drag = pan ยท click = identify
The IV terminal taps the junction of the common and series windings โ€” HV = series + common in series.

Autotransformer design check

First-cut check for an autotransformer: series and common are parts of one winding, with no galvanic isolation. Tender / estimation grade โ€” verify with the manufacturer. Equivalent rating and winding currents, without an impedance split, are on the sizing page.

Method (step-down autotransformer): series voltage = HVโˆ’LV, common = LV; series:common turns = (HVโˆ’LV):LV. Common-winding current Ic = ILV โˆ’ IHV. Self (transformer) rating = Sยท(HVโˆ’LV)/HV โ€” the autotransformer only processes this fraction of throughput, which is why it is smaller. Short-circuit currents use the assumed %Z; the autotransformer's actual %Z is lower than an equivalent two-winding, and the exact IEC 60076-5 value needs the coupled-winding equivalent circuit โ€” treat the impedance figures as first-cut.