Autotransformer equivalent rating
Equivalent (self) rating and the series and common winding currents for a three-phase autotransformer. The co-ratio is 1 − VLV/VHV. Percent impedance is not split, and this page does not show a turns ratio.
Method
The co-ratio α = (VHV − VLV) / VHV is the fraction of throughput that is transformed. IEEE C57.12.10 uses that co-ratio for the equivalent two-winding (self) rating: Seq = Sthrough × α. The rest of the throughput is conducted, which is why the autotransformer is smaller than a two-winding unit of the same throughput.
Three-phase line current is I = S / (√3 · U), the rated-current relationship in IEC 60076-1. Series-winding current equals the HV line current. Common-winding current is ILV − IHV, which is ILV × α. Voltages are line-to-line. This sheet is three-phase only.
Percent impedance referred to the same throughput is not divided by the square of the voltage ratio. A single uk% is not split into a common-winding impedance on this page.