DGA oil-test interpreter

Enter the laboratory ppm values. The page screens them with four published methods. The tool is free. A PDF of the same result is $19.

This is not a substitute for expert diagnosis. One sample cannot show a trend. Compare the result with the transformer's own history and with the limits in the equipment specification.

Optional $19 PDF report

The PDF repeats the inputs and the four readings. Payment does not change the free result on this page.

$19 PDF report

After payment, the download page checks the Stripe session and builds the PDF from the values saved in this browser, or from the same values in the page address.

Methods

Duval Triangle 1. Methane, ethylene, and acetylene are converted to a percent of their sum. The zone is PD, T1, T2, T3, D1, D2, or DT, using the limits published with IEC 60599. The triangle is for identifying a suspected fault. It is not, by itself, proof that a fault exists.

Rogers ratios. CH4/H2, C2H2/C2H4, and C2H4/C2H6 are coded with the IEC 60599 table. A code set that is not in that table is reported as no matching case. A ratio is not formed when both gases in the pair are zero.

IEEE C57.104-2019 status. Each gas is compared with Table 1 (90th percentile) and Table 2 (95th percentile) for the O2/N2 column and age band you select. At or below Table 1 is status 1 on levels. Between the tables is status 2. Above Table 2 is status 3. Tables 3 and 4 need an earlier sample, so they are not applied. A single sample cannot show active gassing. When O2/N2 is unknown, the page uses the column for a ratio at or below 0.2 and says so.

Key-gas method. IEEE C57.104-2019 Annex D.1. The gas with the highest multiple of its Table 1 norm, among acetylene, hydrogen, ethylene, and carbon monoxide, is the key gas when that multiple is above 1. The annex says an automatic reading is often inconclusive.