Transformer Design & Calculation Workbench
Distribution (oil) · Power (oil) · Cast Resin (dry) — an analytical transformer-design workspace using IEC-referenced methods (first-cut sizing, not a certified compliance tool)
🔒 Runs entirely in your browser — zero server calls, zero external AI models, completely client-side and private.
Engineering Review Notice: This is an analytical, first-pass design workspace (BETA). Calculations — core area, turns, conductor sizing, losses, impedance, thermal, impulse and short-circuit figures — provide rapid exploratory sizing based on IEC 60076 principles. All outputs must be checked against the applicable project specification, current published standards, and verified by a qualified design engineer before fabrication.
Validation example — full design.
Inputs: 1,000 kVA, 50 Hz, 11,000 / 433 V, Dyn11, K = 0.45, peak flux 1.70 T, current density 3.0 A/mm² LV and 3.2 A/mm² HV, tap ±5%.
Expected: LV turns 18, HV turns 792, HV turns at +5% tap 832, volts per turn 13.888 V, net core area 368.0 cm², LV line current 1,333.4 A, HV line current 52.49 A, HV winding current 30.30 A, conductor area 444.5 mm² LV and 9.47 mm² HV, insulation level 75 / 28 kV.
References: IEC 60076-1 line current I = S / (√3 · U). Dyn11 is delta on HV, so the HV winding current is the line current divided by √3, and star on LV, so the LV winding current is the line current. Turns are phase voltage divided by volts per turn; volts per turn is then the LV phase voltage divided by the rounded LV turn count. Net core area uses E = 4.44 · f · B · A. The 75 kV lightning impulse and 28 kV AC withstand are the IEC 60076-3 levels for Um 12 kV. K√kVA is this page’s empirical starting volts per turn, not an IEC constant. Loss, weight and impedance on the workbench are first-pass estimates and are outside this check.