Volume 21 is safe work, fire, oil, noise, and the life-cycle footprint. This module separates four specification lines that are often written as slogans. It does not certify a liquid, a bund, or a noise level, and it does not offer an environmental claim for a product. The limit that applies is the limit in the regulation and the contract that govern the site.
Fire and containment are different duties
A liquid’s fire point changes how a fire can start and how it behaves. Mineral oil, natural ester, synthetic ester, and silicone are different liquids with different specifications. Choosing one for fire behaviour does not automatically satisfy a temperature-rise design written for another, and it does not remove the need to contain a spill. Containment — a bund, a tank, a separator — is about where the liquid goes if it leaves the transformer. A high fire point does not absorb a spill. Write the fire requirement and the containment requirement as two lines, each with the rule that applies at the site.
Noise is a guarantee with a stated measure: sound power or sound pressure, the cooling stage that was running, and the distance or the surface the figure uses. A decibel number with none of those is not a guarantee you can test. Load noise and no-load noise are different. A unit that meets a no-load figure can miss the figure once the fans are on. End of life is a materials question: what is in the tank, what can be reprocessed, and what has to be handled as waste under the rule that applies. It is not a slogan on the front of a brochure, and this course does not assign a recycling rate.
The site rule outranks a catalogue line
Indoor installation, a basement, a tunnel, or a place where people work beside the unit can exclude a liquid or demand a fire behaviour the catalogue unit does not have. The answer is in the site’s rules and in the contract, not in a general preference for one technology. Dry-type construction avoids a liquid spill and brings its own fire, temperature, and clearance questions, which the dry-type standard addresses. This module does not choose between them. It asks that the enquiry say which hazard it is buying down.
- Fire point and spill containment are two requirements. Meeting one does not meet the other.
- Name the liquid. Do not carry a mineral-oil thermal design onto an ester without redesign.
- A noise guarantee needs the measure, the cooling stage, and the distance or surface.
- End of life follows the waste rule at the site. Do not invent a recovery rate.