What Are the Common Causes of Transformer Failure?
Insulation and winding
Thermal aging and overheating break down the cellulose; moisture lowers the dielectric strength; winding deformation or inter-turn faults arise from short-circuit forces. These show up as DGA gases (ethylene, carbon oxides, hydrogen, acetylene).
Tap-changer and leads
OLTC contact, diverter and mechanism faults are a leading cause, often seen as acetylene in the oil. Loose or broken leads and terminations also fail under load and vibration.
Environmental and operational
Lightning and switching surges damage the insulation; overloading and loss of cooling overheat the unit; contamination and oil degradation (sludge, moisture, acidity) accelerate aging.
Prevention
Routine DGA, oil and insulation tests (power factor, PD, moisture), thermography, and monitoring of temperature, cooling and tap-changer condition catch most failures before they escalate.
References & standards
- IEC 60599
- IEEE C57.104